为你详细介绍产品中心的产品内容,包括产品中心的用途、型号、范围、图片等,在这里你可以得知产品中心的新闻以及市场产品中心价格。

Product center

MNS low pressure draw-out switchgear

MNS low pressure draw-out switchgear

  • The MNS type low-voltage withdrawable switchgear (hereinafter referred to as the switchgear) was developed by our company after referring to the MNS series low-voltage sw...
  • Product overview
  • Model and features
  • Technical parameter
  • Overall dimension

Product overview

The MNS type low-voltage withdrawable switchgear (hereinafter referred to as the switchgear) was developed by our company after referring to the MNS series low-voltage switchgear of the Swiss ABB company and making comprehensive improvements. It is currently the most advanced low-voltage withdrawable switchgear in the country. This product is composed of standardized and series modules, and the drawers have reliable mechanical interlocking devices, making them safer and more reliable for users to use.

This switch cabinet is suitable for three-phase five-wire power supply systems with AC 50 (60) Hz, rated operating voltage 400V, 660V, and rated current 5000A and below. It can be used in power plants, substations, industrial and mining enterprises, building hotels, and airports. , docks, radio and television and other communication centers to control power generation, transmission and distribution, power conversion and power consumption equipment, and reactive power compensation is performed on its main bus through the capacitor compensation cabinet.

This product complies with the requirements of GB7251.12-2013 "Low-voltage complete switchgear and control equipment", IEC61439-2:2011 "Low-voltage complete switchgear and control equipment" and other standards.


Model and features



Normal service conditionsNormal service conditions


 Ambient temperature: upper limit +40°C, lower limit -15°C (up to -45°C with special technology);

 The altitude does not exceed 2500m (with special technology, it can reach 4000m);

 The relative humidity of the surrounding air does not exceed 50% when the maximum temperature is +40°C. It has a higher relative humidity at lower temperatures, such as 90% at +20°C, but considering that it may be possible due to temperature changes Moderate condensation may occasionally occur.

 Should be installed in a place where there is no severe vibration or impact, and where electrical components are not subject to corrosion.

Note: When the above normal usage conditions are exceeded, the user can negotiate with the manufacturer to determine.

Technical parameter


过电压类别
Overvoltage category
IV Ill
污染等级
Pollution Degree
3
额定工作电压(Ue)(V) Rated operating voltage 400/660
额定绝缘电压(Ui)(V) Rated insulation voltage 660/1000
额定频率(Hz)
Rated frequency
50(60)
水平母线 Horizontal busbar 额定电流
Rated Current
≤5000A
额定短时耐受电流(lcw)(kA) Rated short-time withstand current 50,65,80(1s有效值rms)
额定峰值耐受电流(lpk)(kA) Rated peak withstand current 105,140, 176(0.1s最大值Maximum)
垂直母线 Vertical busbar 额定最大工作电流
Rated maximum operating current
≤1000A
额定短时耐受电流
Rated short-time withstand current
50kA
额定峰值耐受电流
Rated peak withstand current
105kA
外壳防护等级
Degree of protection
IP30 IP40(特殊说明special Instructions)

Overall dimension


Structure and DimensionsStructure and Dimensions

The MNS series switch cabinet is installed vertically, not against the wall. Behind it is the outlet cable trench of the cabinet. To facilitate maintenance, the distance from the back to the wall is usually 800~1200mm. For installation from the front, see the figure below.